DocumentCode
1027393
Title
Surge Potentials on Underground Cable Sheath and Joint Insulation
Author
Watson, W. ; Erven, C.C.
Author_Institution
Hydro-Electric Power Commission of Ontario
Volume
82
Issue
66
fYear
1963
fDate
6/1/1963 12:00:00 AM
Firstpage
239
Lastpage
249
Abstract
Insulating sheath coatings and sheath-joint insulators have been punctured in service, apparently by transient voltages. It has been shown that the discontinuities caused by sheath cross-bonding result in 15% of an applied surge on a conductor, appearing on the sheath at a joint and 30% across the sheath insulator. Bonding transformers result in higher transients. Protective devices appear to be required at each joint. These may be lightning arresters or surge capacitors.
Keywords
Arresters; Bonding; Cable insulation; Cable shielding; Capacitors; Coatings; Conductors; Lightning; Power transformer insulation; Surge protection;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1963.291348
Filename
4072789
Link To Document