Title : 
Surge Potentials on Underground Cable Sheath and Joint Insulation
         
        
            Author : 
Watson, W. ; Erven, C.C.
         
        
            Author_Institution : 
Hydro-Electric Power Commission of Ontario
         
        
        
        
        
            fDate : 
6/1/1963 12:00:00 AM
         
        
        
        
            Abstract : 
Insulating sheath coatings and sheath-joint insulators have been punctured in service, apparently by transient voltages. It has been shown that the discontinuities caused by sheath cross-bonding result in 15% of an applied surge on a conductor, appearing on the sheath at a joint and 30% across the sheath insulator. Bonding transformers result in higher transients. Protective devices appear to be required at each joint. These may be lightning arresters or surge capacitors.
         
        
            Keywords : 
Arresters; Bonding; Cable insulation; Cable shielding; Capacitors; Coatings; Conductors; Lightning; Power transformer insulation; Surge protection;
         
        
        
            Journal_Title : 
Power Apparatus and Systems, IEEE Transactions on
         
        
        
        
        
            DOI : 
10.1109/TPAS.1963.291348