Static Mho Distance and Pilot Relaying
Author :
Caleca, V. ; Horowitz, S.H. ; McConnell, A.J. ; Seeley, H.T.
Author_Institution :
American Electric Power Service Corporation
Volume :
82
Issue :
67
fYear :
1963
Firstpage :
424
Lastpage :
436
Abstract :
The functional requirements for high-speed transmission-line relaying are outlined, and a new principle for coordinating ultrahigh-speed tripping units in a pilot relay system is described. Application to 3-terminal lines is reviewed in principle and illustrated by an example. Factory and field tests and a lightning season´s field experience are recorded, showing tripping times of 6 to 16 msec (milliseconds) for the pilot relaying and 0.1 to 15 msec for the phase-backup relaying.
Keywords :
Circuit breakers; Costs; Investments; Lightning; Production facilities; Protective relaying; Relays; Springs; System testing; Transmission lines;