Title : 
Field Measurement of 345-Kv Lightning Arrester Switching Surge Perrormance
         
        
            Author : 
Price, W.S. ; McElroy, A.J. ; Smith, H.M. ; Shankle, D.F.
         
        
            Author_Institution : 
American Electric Power Service Corporation
         
        
        
        
        
        
        
            Abstract : 
The purpose of this paper is to present lightning arrester switching surge voltages and currents, measured during a field test program on a 345-kv system. Surges were produced by energization of a transformer-terminated line and by ultra-high-speed re-energization (UHSR) of arrester-terminated lines. Arrester-sparkover levels were 1.1 to 1.7 pu (per unit) of arrester rating, and arrester follow-current peaks were 135 to 940 amperes.
         
        
            Keywords : 
Analog computers; Arresters; Continuous improvement; Costs; Current measurement; Lightning; Power transformer insulation; Shape; Surge protection; System testing;
         
        
        
            Journal_Title : 
Power Apparatus and Systems, IEEE Transactions on
         
        
        
        
        
            DOI : 
10.1109/TPAS.1963.291442