• DocumentCode
    1027832
  • Title

    500-Kv-Line Design

  • Author

    Johnson, W.R. ; Lambert, E.G. ; Tice, J.B. ; Turner, F.J.

  • Author_Institution
    Pacific Gas and Electric Company
  • Volume
    82
  • Issue
    67
  • fYear
    1963
  • Firstpage
    581
  • Lastpage
    587
  • Abstract
    The results of full-scale transmission-tower switching-surge, impulse, and 60-cycle tests, wet and dry, indicate pronounced departure from previously published data where the effect of the proximity of the tower was not included. The data include single-insulator strings, V-strings, and lhorizontal and vertical tower gaps including guy-wire gaps. These data are an extension of previous studies on Project EHV insulation structures1 and were undertaken to provide design criteria for a 100-mile link of 500-kv line running at an average elevation of 5,000 feet between Klamath Falls, Oreg., anid Round Mountain, Calif.
  • Keywords
    Contamination; Cranes; Geometry; Impulse testing; Insulation; Laboratories; Leg; Personnel; Poles and towers; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1963.291453
  • Filename
    4072835