DocumentCode :
1029077
Title :
Corona-Loss Characteristics of EHV Transmission Lines Based on Project EHV Research
Author :
Anderson, J.G. ; Baretsky, M., Jr. ; Maccarthy, D.D.
Author_Institution :
General Electric Company
Issue :
12
fYear :
1966
Firstpage :
1196
Lastpage :
1212
Abstract :
Since 1960 the corona-loss characteristics of a variety of extra-high-voltage (EHV) transmission-line configurations have been under study at Project EHV [1], [2]. This paper presents results from the analysis of corona losses measured under all weather conditions experienced during 2¿years of observation of single or bundled conductors at 500 or 700 kV. In addition, corona characteristics are presented for switching-surge transients and severe steady-state overvoltages. The purpose of this paper is: 1) to summarize some of the statistical aspects of fair-and foul-weather corona-loss observations for the configurations studied, and 2) in terms of electrical and meteorological parameters, to describe an equation for corona loss on EHV lines that is in a form directly applicable by transmission engineers to EHV-line design.
Keywords :
Conductors; Corona; Equations; Loss measurement; Meteorology; Power system transients; Steady-state; Surges; Transmission line measurements; Transmission lines;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1966.291639