• DocumentCode
    1029775
  • Title

    Transient Characteristics or Current Transformers During Faults-II

  • Author

    Rothe, F.S. ; Concordia, C.

  • Author_Institution
    General Electric Company, Schenectady, N. Y.
  • Volume
    66
  • Issue
    1
  • fYear
    1947
  • Firstpage
    731
  • Lastpage
    734
  • Abstract
    The range of application of current transformers in bus differential protective systems is limited by saturation in the transformer cores under fault conditions, which may sometimes result in improper relay operations. It is shown that the addition of impedance in the relay circuit will reduce the relay current under fault conditions so as to increase the range of applications for which standard current transformers may be used.
  • Keywords
    Circuit faults; Current transformers; Fault currents; Impedance; Proposals; Protection; Protective relaying; Relays; Transformer cores; Transient analysis;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1947.5059499
  • Filename