DocumentCode :
1030054
Title :
Full-Scale Tests for the Allegheny Power System 500-kV Tower-Insulation System
Author :
Guyker, W.C. ; Hileman, A.R. ; Wittibschlager, J.F.
Author_Institution :
West Penn Power Company
Issue :
6
fYear :
1966
fDate :
6/1/1966 12:00:00 AM
Firstpage :
614
Lastpage :
623
Abstract :
Switching surge, impulse, and 60-cycle tests performed on the APS 500-kV tower-insulation system proved the adequacy of the design which consisted of twenty-four53/4 X 10-inch insulators in V-string configuration with an 11-foot 2-inch minimum strike distance. The minimum switching surge withstand voltage is 965 kV. Minimum impulse critical flashover voltage is 1890 kV, and the minimum 60-cycle flashover and withstand voltages are 707 kV and 660 kV rms, respectively. The switching surge test results from the full-scale tower agreed closely with those predicted from simulated tower-insulation tests. The switching surge flashover probability curve tends to follow the equations for a normal cumulative distribution curve to about the 2 to 5 percent probability level, whereas previous test results showed correlation only to the 5 to 10 percent probability level.
Keywords :
Flashover; Impulse testing; Insulation; Insulator testing; Performance evaluation; Poles and towers; Power systems; Surges; System testing; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1966.291597
Filename :
4073089
Link To Document :
بازگشت