DocumentCode
1030431
Title
Transformer Corona Testing
Author
Meador, J.R. ; Kaufman, R.B. ; Brustle, H.H.
Author_Institution
General Electric Company
Issue
8
fYear
1966
Firstpage
893
Lastpage
900
Abstract
The progress made to date in corona testing transformers at the factory is reviewed and the importance of sonic detection and location of corona sources is shown. Major improvements in sonic techniques are reported. Test curves of RIV vs. transformer test voltage are given for units having defects. The various corona test proposals being considered by the industry are described and discussed. The best assurance of product quality is stated to be a corona test, using RIV and advanced sonic techniques, made at full transformer induced test voltage with a limit of 1000 microvolts.
Keywords
Capacitance measurement; Capacitors; Circuit testing; Corona; Electrical equipment industry; Insulators; Power transformer insulation; Power transformers; Production facilities; Proposals;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1966.291630
Filename
4073131
Link To Document