DocumentCode :
1030942
Title :
Ferroresonant Overvoltage Control Based on TNA Tests on Three-Phase Delta - Wye Transformer Banks
Author :
Hopkinson, Ralph H.
Author_Institution :
General Electric Company
Issue :
10
fYear :
1967
Firstpage :
1258
Lastpage :
1265
Abstract :
Possible ferroresonant overvoltages are shown on delta- wye transformer banks during single-phase switching as a function of transformer size and lateral length. The application guide is based on industry standard voltage criteria. Secondary loading requirements are given. Simple to use equations are given to allow application of test data.
Keywords :
Cable shielding; Capacitors; Control systems; Electrical equipment industry; Equations; Ferroresonance; Switching circuits; Testing; Transient analysis; Voltage control;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1967.291902
Filename :
4073191