• DocumentCode
    1031821
  • Title

    A practical protective relay for down-conductor faults

  • Author

    Jeerings, D.I. ; Linders, J.R.

  • Author_Institution
    Nordon R&D Inc., Plant City, FL, USA
  • Volume
    6
  • Issue
    2
  • fYear
    1991
  • fDate
    4/1/1991 12:00:00 AM
  • Firstpage
    565
  • Lastpage
    574
  • Abstract
    A practical relay for detecting down-conductor high-impedance ground faults (HIGF) is described, with supporting theory and data from live line tests. The use of the third-harmonic current magnitude and the phase relation to the system voltage is shown to provide useful information for detecting this type of fault. By suppressing ambient harmonics and utilizing only the change in the harmonics, a fault current sensitivity of 1% of the feeder rating is shown to be feasible. Fault detection concepts include harmonic phase sequence components in the three-phase unit. Relays for both single-phase laterals and three-phase circuits are described. Redundant measurement techniques in both versions are shown to enhance the reliability of the system and to contribute to the feasibility of the noted sensitivity
  • Keywords
    electrical faults; relay protection; ambient harmonics; down-conductor faults; fault current sensitivity; feeder rating; high-impedance ground faults; protective relay; reliability; third-harmonic current magnitude; Circuit faults; Electrical fault detection; Fault currents; Fault detection; Phase detection; Protection; Protective relaying; Relays; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.131113
  • Filename
    131113