DocumentCode
1032117
Title
Laboratory and Service Aging Tests of Paper - Insulated, Three-Conductor Cables for 12-kV Service
Author
Adler, H.A. ; Halperin, Herman
Author_Institution
Commonwealth Edison Company
Issue
5
fYear
1967
fDate
5/1/1967 12:00:00 AM
Firstpage
592
Lastpage
603
Abstract
Forty 3-conductor cables for 12-kV service were subjected to stability studies in laboratory aging tests and/or in experimental service operation. The main purpose for this was the determination of 1) difference between the stability of shielded and of belted cables, 2) minimum safe insulation thickness for shielded cables, and 3) maximum permissible temperatures for normal and emergency operation. The results showed superiority of shielded cables and marked effects of insulation thickness and temperatures upon stability.
Keywords
Aging; Cable insulation; Cable shielding; Cables; Conductors; Laboratories; Seals; Stability; Temperature; Testing;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1967.291736
Filename
4073321
Link To Document