DocumentCode :
1032297
Title :
On-site dielectric testing of GIS: theoretical and practical considerations
Author :
Feser, K. ; Sun, Rui ; Eriksson, A. ; Frohlich, K.
Author_Institution :
Stuttgart Univ., Germany
Volume :
6
Issue :
2
fYear :
1991
fDate :
4/1/1991 12:00:00 AM
Firstpage :
615
Lastpage :
625
Abstract :
After reviewing the primary objectives of on-site testing of GISs, (gas-insulated substations), the authors provide an analysis of practical experience in the use of several alternative test techniques in a large sample of operational GIS installations. It is observed that AC tests thus far have been the most effective. Consideration of the physical background, however, supports the inclusion also of a lightning impulse voltage test, but with the test level strictly limited in order to take account of the associated very fast transients which could arise in the event of test flashover. Recommendations for an amended on-site test approach for GIS are presented, together with comments on the implications for further research on measurement techniques
Keywords :
flashover; gaseous insulation; substations; testing; GIS; gas-insulated substations; lightning impulse voltage test; on-site dielectric testing; test flashover; transients; Construction; Dielectrics and electrical insulation; Gas insulation; Geographic Information Systems; Impulse testing; Lightning; Production facilities; Quality control; Substations; Voltage;