  • Abstract
    The results of two different series of life tests carried out on vacuum switches with a self-produced axial magnetic field (in view of their use in nuclear fusion facilities) are presented. The goal was to obtain a large number (on the order of 2000) of interruptions of a unidirectional current of over 50 kA, with a recovery voltage of up to 35 kV. A first series of tests showed that the test procedure with an accelerated life test was not adequate; it was also apparent that the contact plate, designed for 50 Hz applications, had weak points when subjected to extended thermal contacts. Therefore, a new version of the switches, with modified contacts, was built. Both versions of the switches were tested with a new test procedure, and satisfactory test results were obtained
  • Keywords
    life testing; switchgear; vacuum apparatus; 35 kV; 50 kA; life testing; recovery voltage; self-produced axial magnetic field; thermal contacts; unidirectional current; vacuum switches; Automatic testing; Energy exchange; Fusion reactors; Life testing; Magnetic fields; Magnetic switching; Switches; Thermal stresses; Variable structure systems; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.131141
  • Filename
    131141