DocumentCode
1032542
Title
Post arc currents in medium voltage interrupting devices
Author
Girard, Alain ; Bernard, Georges ; Malkin, Peter
Author_Institution
Merling Gerin, Grenoble, France
Volume
6
Issue
2
fYear
1991
fDate
4/1/1991 12:00:00 AM
Firstpage
849
Lastpage
857
Abstract
Current zero measurements in modern circuit breakers are discussed. It is shown that vacuum interrupters always exhibit a postarc current when breaking at high current. On the other hand, it is shown that, due to the very short time constant of SF6 circuit breakers, no measurable postarc current is driven in these devices. A description of the current zero phenomena in SF6 is proposed, which includes the interaction with the circuit. It is noted that O. Mayr´s (1943) and A. M. Cassie´s (1939) models are not sufficient for describing the current zero phase
Keywords
circuit breakers; electric current measurement; gaseous insulation; sulphur compounds; vacuum apparatus; MV interrupting devices; SF6 circuit breakers; current zero measurements; post arc currents; postarc current; vacuum interrupters; Bandwidth; Cooling; Current measurement; Interrupters; Medium voltage; Societies; Sulfur hexafluoride; Switchgear; Testing; Time measurement;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.131144
Filename