• DocumentCode
    1032633
  • Title

    Influence of Air Density on Electrical Strength of Transmission Line Insulation

  • Author

    Phillips, T.A. ; Robertson, Lawrence M. ; Rohlfs, Albert F. ; Thompson, Richard L.

  • Author_Institution
    Arizona Public Service Company
  • Issue
    8
  • fYear
    1967
  • Firstpage
    948
  • Lastpage
    961
  • Abstract
    Flashover tests were conducted at the Leadville EHV Test Facility of the Public Service Company of Colorado and Project EHV at Pittsfield, Mass., to obtain comparative data to evaluate the influence of air density on switching surge and impulse flashover strength of transmission line insulation. The tests showed that negative polarity flashover voltages are greater than those of positive polarity. Therefore, positive polarity will be the critical requirement for transmission line design for switching surge duty.
  • Keywords
    Dielectrics and electrical insulation; Flashover; Humidity; Insulation testing; Ocean temperature; Poles and towers; Surges; System testing; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1967.291918
  • Filename
    4073375