DocumentCode :
1032633
Title :
Influence of Air Density on Electrical Strength of Transmission Line Insulation
Author :
Phillips, T.A. ; Robertson, Lawrence M. ; Rohlfs, Albert F. ; Thompson, Richard L.
Author_Institution :
Arizona Public Service Company
Issue :
8
fYear :
1967
Firstpage :
948
Lastpage :
961
Abstract :
Flashover tests were conducted at the Leadville EHV Test Facility of the Public Service Company of Colorado and Project EHV at Pittsfield, Mass., to obtain comparative data to evaluate the influence of air density on switching surge and impulse flashover strength of transmission line insulation. The tests showed that negative polarity flashover voltages are greater than those of positive polarity. Therefore, positive polarity will be the critical requirement for transmission line design for switching surge duty.
Keywords :
Dielectrics and electrical insulation; Flashover; Humidity; Insulation testing; Ocean temperature; Poles and towers; Surges; System testing; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1967.291918
Filename :
4073375
Link To Document :
بازگشت