DocumentCode :
1032857
Title :
An Experimental Investigation of the Electrical Performance of Bolted Aluminurm-to-Copper Connections
Author :
Bonwitt, W.F.
Author_Institution :
Burndy Engineering Company, New York, N. Y.
Volume :
67
Issue :
2
fYear :
1948
Firstpage :
1208
Lastpage :
1219
Abstract :
Bolted bus connections between bare aluminum and copper, with an electrotinned and flowed finish, will provide a low-resistance joint which will be reasonably stable even under extreme conditions of elevated temperature and corrosive attack. While the use of a compound, Penetrox ``A,´´ will greatly improve and stabilize the contact conditions, the combination of aluminum and copper (electrotinned and flowed), will form a satisfactory electric connection even when made without the use of any compound.