DocumentCode
1033352
Title
Dielectric Tests on EHV Pantograph Switches
Author
Yee, William F.
Author_Institution
Allis-Chalmers Manufacturing Company
Issue
10
fYear
1968
Firstpage
1813
Lastpage
1819
Abstract
Tests were conducted on pantograph type disconnect switches to determine their dielectric characteristics. The data includes switching surge, impulse, and power frequency tests on insulations of 1300-, 1550-, and 1925-kV BIL, and open gaps of 130, 160, 180, and 200 inches. A comparison between the pantograph gap characteristics and various other vertical gaps, as well as vertical break switch gaps, is made. The effects of water resistivity on wet switching surge characteristics of the switch insulators was investigated for a 1550-kV BIL stack. The data is useful as a guide to the application of pantograph switches for EHV.
Keywords
Conductivity; Costs; Dielectric breakdown; Dielectrics and electrical insulation; Impulse testing; Insulator testing; Substations; Surges; Switches; Water;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1968.292141
Filename
4073452