• DocumentCode
    1033542
  • Title

    New Measurement of Synchronous Machine Quantities

  • Author

    Kaminosono, Hiroshi ; Uyeda, Kiyotaka

  • Author_Institution
    Central Research Institute of Electric Power Industry
  • Issue
    11
  • fYear
    1968
  • Firstpage
    1908
  • Lastpage
    1918
  • Abstract
    Synchronous machine quantities are used in the various studies of power system behavior under both normal and abnormal conditions. Instead of the IEEE test code 115 [1] generally employed, this paper describes two approaches to measure synchronous machine quantities of each winding with the machine at standstill, namely, the indicial response method and the low-requency response method. These quantities are directly applicable as various coefficients in Park´s equation of synchronous machine. Comparison with conventional methods and analysis in the short-circuit phenomena lead to the fact that it suffices to consider that both direct and quadrature axes each have one damper circuit and that the time constant of the damper winding and the coupling coefficients between windings can be considered almost constant in the low-frequency region (0-0.1 pu).
  • Keywords
    Circuit faults; Coupling circuits; Equations; Machine windings; Power system measurements; Power system transients; Synchronous machines; Testing; Transient analysis; Transmission line measurements;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.292012
  • Filename
    4073472