• DocumentCode
    1034303
  • Title

    Japanese Method of Artificial Pollution Tests on Insulators

  • Author

    Fujitaka, Shuhei ; Kawamura, Tatsuo ; Tsurumi, Sakuro ; Kondo, Hiroshi ; Seta, Taisuke ; Yamamoto, Mitsuyoshi

  • Author_Institution
    University of Tokyo
  • Issue
    3
  • fYear
    1968
  • fDate
    3/1/1968 12:00:00 AM
  • Firstpage
    729
  • Lastpage
    735
  • Abstract
    Salt pollution on outdoor insulators has been a serious problem in Japan, and steady efforts have been made to prevent flashover faults on polluted insulators. As a part of such efforts, a simple method of artificial pollution test has been developed to evaluate the flashover characteristics of polluted insulators, especially those with large dimensions. In this test, a salt solution of various concentrations containing a certain amount of kaolin is prepared and sprayed on the entire surface of the insulator to give a required density of salt deposit and sufficient moisture.
  • Keywords
    Flashover; Insulation; Insulator testing; Marine pollution; Pollution measurement; Sea measurements; Sea surface; Spraying; Surface contamination; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.292186
  • Filename
    4073556