• DocumentCode
    1034976
  • Title

    Field and Laboratory Tests of Contaminated Insulators for the Design of the State Electricity Commission of Victoria´s 500-kY System

  • Author

    Johnson, John ; Henderson, Roy T. ; Price, William S. ; Hedman, Dale E. ; Turner, Frederick J.

  • Author_Institution
    State Electricity Commission of Victoria
  • Issue
    5
  • fYear
    1968
  • fDate
    5/1/1968 12:00:00 AM
  • Firstpage
    1216
  • Lastpage
    1239
  • Abstract
    The results of field and laboratory tests on contaminated insulators, made to determine insulation level of the State Electricity Commission of Victoria´s 500-kV transmission system, are presented, including performance of 220-kV lines operating in a very heavy contamination area, field measurements of the pollution and insulator flashover mechanism, development of artificial pollution for laboratory tests, and the use of this pollution for power frequency and switching surge tests at the General Electric Pittsfield High Voltage Laboratory. Test data include curves of power frequency and switching surge flashover levels versus contamination severity; power frequency flashover versus string length; and the results of high-speed motion picture tests made to determine the basic mechanism of critical surging and flashover on contaminated insulators, plus a theoretical explanation of this mechanism.
  • Keywords
    Contamination; Dielectrics and electrical insulation; Flashover; Frequency; Insulation testing; Insulator testing; Laboratories; Pollution; Surges; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.292212
  • Filename
    4073625