• DocumentCode
    1035793
  • Title

    Thermal Performance of Distribution Transformers in Underground Vaults: II - Mathematical Model

  • Author

    Whirlow, Donald K. ; Lockie, Arthur M.

  • Author_Institution
    Westinghouse Electric Corporation
  • Issue
    9
  • fYear
    1968
  • Firstpage
    1745
  • Lastpage
    1754
  • Abstract
    The transient thennal response of buried distribution transformers is analyzed by use of a lumped-parameter model. Curves are presented which show the temperatures in the transformer r during startup and continuous running with typical load cycles, steady loads, and step loads. The effects of earth conductivity y and radiation barriers are considered. Temperatures, time constants, and convection coefficients are found to agree well with experimental measurements.