    Screening Factor of Pipe-Type Cable Systems

  • Author

    Chu, S.C.

  • Author_Institution
    Enfield-Standard Power Cables Ltd.
  • Issue
    5
  • fYear
    1969
  • fDate
    5/1/1969 12:00:00 AM
  • Firstpage
    522
  • Lastpage
    528
  • Abstract
    After reviewing the background of zero sequence impedance of pipe-type cables, the paper describes in general the longitudinal voltages induced in adjacent auxiliary cables due to a fault in power transmission systems. The magnitude of the induced voltage is influenced by the screening effect of the power cables. The screening factor and the impedance of the steel pipe have been measured in the laboratory by short-circuit tests on a 275-kV cable sample with a simulated ground return path. The results are used to illustrate the application in induced voltage calculations in a typical example.