DocumentCode :
1037184
Title :
Insulations and Jackets for Control and Power Cables in Thermal Reactor Nuclear Generating Stations
Author :
Blodgett, Robert B. ; Fisher, Robert G.
Author_Institution :
The Okonite Company
Issue :
5
fYear :
1969
fDate :
5/1/1969 12:00:00 AM
Firstpage :
529
Lastpage :
541
Abstract :
The permanent change in the physical strengths, rate of oxidation, dielectric loss, and electrical stability in 40-psig (142??C) steam and dielectric strength are reported for 13 elastomer-based insulation-jacket combinations after irradiation up to 108 rad in air at 5 ??105 rad/h from a cobalt 60 source. Threshold of damage for each property, overall threshold of damage, and highest dose rate still serviceable for the combinations are summarized. On the basis of these date, suggestions are made for IEEE nuclear environment classification of cable coverings rate for continuous 90??C and higher.
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1969.292321
Filename :
4073865
Link To Document :
بازگشت