DocumentCode
1039044
Title
Arc-Fault Characteristics of Bare Overhead Distribution Conductors: Seven-Strand AAAC (6201) and 6/1 ACSR
Author
Hazan, Earl
Author_Institution
Kaiser Aluminum Company
Issue
3
fYear
1970
fDate
3/1/1970 12:00:00 AM
Firstpage
411
Lastpage
420
Abstract
The results of a series of tests on three different AWG sizes of bare seven-strand AAAC (6201) conductors and bare 6/1 ACSR conductors are outlined. Since arc-fault characteristics have not been subjected to rigorous engineering analysis, an experimental investigation was required to determine how such conductors reacted to arc faults of various intensities. Investigation revealed that the AAAC (6201) and 6/1 ACSR conductors were equivalent in their resistance to arcing faults. In addition, we found that hot-spot temperatures resulted from severed strands. The hot-spot temperatures that developed in the 6/1 ACSR conductors were significantly higher than those developed in the seven-strand AAAC (6201) conductors when these conductors carried equal steady-state current.
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1970.292717
Filename
4074066
Link To Document