• DocumentCode
    1039044
  • Title

    Arc-Fault Characteristics of Bare Overhead Distribution Conductors: Seven-Strand AAAC (6201) and 6/1 ACSR

  • Author

    Hazan, Earl

  • Author_Institution
    Kaiser Aluminum Company
  • Issue
    3
  • fYear
    1970
  • fDate
    3/1/1970 12:00:00 AM
  • Firstpage
    411
  • Lastpage
    420
  • Abstract
    The results of a series of tests on three different AWG sizes of bare seven-strand AAAC (6201) conductors and bare 6/1 ACSR conductors are outlined. Since arc-fault characteristics have not been subjected to rigorous engineering analysis, an experimental investigation was required to determine how such conductors reacted to arc faults of various intensities. Investigation revealed that the AAAC (6201) and 6/1 ACSR conductors were equivalent in their resistance to arcing faults. In addition, we found that hot-spot temperatures resulted from severed strands. The hot-spot temperatures that developed in the 6/1 ACSR conductors were significantly higher than those developed in the seven-strand AAAC (6201) conductors when these conductors carried equal steady-state current.
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1970.292717
  • Filename
    4074066