• DocumentCode
    1039109
  • Title

    Strength Characteristics of Air Gaps Subjected to Interphase Switching Surges

  • Author

    Cortina, Rosario ; Sforzini, Mario ; Taschini, Achille

  • Author_Institution
    Ente Nationale per l´´Energia Elettrica (ENEL)
  • Issue
    3
  • fYear
    1970
  • fDate
    3/1/1970 12:00:00 AM
  • Firstpage
    448
  • Lastpage
    452
  • Abstract
    The present philosophy in the selection of phase-to- phase clearances has been examined. On the basis of a number of oscillograms of switching surges in an EHV system, some characteristics of the overvoltage stresses between phases that have not been considered by the interphase testing methods adopted up to now are demonstrated. By means of a series of switching impulse laboratory tests, it has been shown that these characteristics of thephase-to- phase overvoltages cannot be overlooked in assessing the dielectric strength of phase-to-phase air-insulated structures of substations.
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1970.292722
  • Filename
    4074071