Abstract :
A simple three-phase filter connection that can significantly reduce losses for high-power applications without automatic tuning is presented. It is shown that the fundamental-frequency power losses can, for some cases, be limited to those associated with the filter inductors and capacitors. Perfornance equations for the filter at the fundamental frequency and at resonance are derived, and an example is given.