• DocumentCode
    1040234
  • Title

    The Torsional Damper for Conductors- Service Experience and Further Experimental Work

  • Author

    Burgess, T.J. ; Hogg, A.D.

  • Author_Institution
    The Hydro-Electric Power Commission of Ontario, Toronto, Ont., Canada.
  • Volume
    70
  • Issue
    1
  • fYear
    1951
  • fDate
    7/1/1951 12:00:00 AM
  • Firstpage
    1031
  • Lastpage
    1033
  • Abstract
    Careful inspection of ACSR (steel-reinforced aluminum cable) conductors operating for ten years equipped with torsional dampers has shown no apparent damage due to aeolian vibration. Type HH copper conductor without dampers has been operating for a similar period without trouble. Further experimental work indicates that there is little tendency for ACSR conductors to vibrate at tensions less than 8 per cent of their ultimate strength.
  • Keywords
    Aluminum; Clamps; Conductors; Copper; Damping; Inspection; Mouth; Shock absorbers; Testing; Vibration measurement;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1951.5060521
  • Filename
    5060521