• DocumentCode
    1040499
  • Title

    Transient Current Capacity of Aluminum-Clad Steel Ground Wires

  • Author

    Tanaka, Akira ; Hoshino, Hiroyuki

  • Author_Institution
    Engineering Department of Hitachi Cable Ltd.
  • Issue
    7
  • fYear
    1970
  • Firstpage
    1493
  • Lastpage
    1498
  • Abstract
    In transmission systems in which a large inducing current flows into the overhead ground wires during short-circuit faults, it is essential that these wires have high conductivity. Aluminum alloy conductors, steel reinforced, have been used in the past. However, it has been shown in comparative tests that thick aluminum-clad AS strands have less deterioration of their properties due to short-circuit faults and are much better suited for use as over- head ground wires. Finally, the transient current capacities are given for various types of widely used AS ground wires.
  • Keywords
    Aluminum alloys; Conductivity; Conductors; Electric resistance; Galvanizing; Power system transients; Power transmission lines; Steel; Testing; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1970.292795
  • Filename
    4074225