  • Abstract
    Direct-buried transformer thermal behavior has been studied for 3 years in Ohio. The relationship between a transformer´s loadability and its physical and electrical characteristics has been established for this soil environment. Tests show that small transformers can be direct buried, but larger units require supplementary cooling. A heat exchanger utilizing water as the heat- transfer medium reduces transformer operating temperatures dramatically.
  • Keywords
    Cooling; Electric variables; Moisture; Power transformer insulation; Soil; Temperature; Testing; Thermal conductivity; Thermal resistance; Water heating;