Title :
Direct-Buried Transformer Thermal Tests
Author :
Lucic, Nicholas A.
Author_Institution :
Cleveland Electric Illuminating Company
Abstract :
Direct-buried transformer thermal behavior has been studied for 3 years in Ohio. The relationship between a transformer´s loadability and its physical and electrical characteristics has been established for this soil environment. Tests show that small transformers can be direct buried, but larger units require supplementary cooling. A heat exchanger utilizing water as the heat- transfer medium reduces transformer operating temperatures dramatically.
Keywords :
Cooling; Electric variables; Moisture; Power transformer insulation; Soil; Temperature; Testing; Thermal conductivity; Thermal resistance; Water heating;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1970.292821