    Transient Overvoltages Caused by the Initiation and Clearance of Faults on a 1100-kV System

  • Author

    Colclaser, R. Gerald, Jr. ; Wagner, Charles L. ; Buettner, Donald E.

  • Author_Institution
    Westinghouse Electric Corporation
  • Issue
    8
  • fYear
    1970
  • Firstpage
    1744
  • Lastpage
    1751
  • Abstract
    Overvoltages on UHV systems may be controlled to a level of 1.5 pu or less. Historically, lightning, line energizing, and line reenergizing overvoltages have been the primary factors in establishing power system design levels. At the new reduced levels, other transients must be considered. Fault initiation and fault clearing transients are investigated using different system configurations. Minimum levels are established by fault initiation transients. Fault clearing overvoltages can be controlled to corresponding levels by the insertion of opening resistors.
  • Keywords
    Circuit breakers; Circuit faults; Costs; Insulation; Lightning; Power system transients; Resistors; Surges; Switching circuits; Voltage control;