DocumentCode
1040807
Title
Switching-Surge Flashover of EHV-UHV Towers
Author
Kachler, Adolf J. ; Laforest, James J. ; Zaffanella, Luciano E.
Author_Institution
High Voltage Laboratory, General Electric Company
Issue
8
fYear
1970
Firstpage
1762
Lastpage
1771
Abstract
Design curves are presented for switching-surge flashover of tower window gaps 20 to 39 feet (6.1 to 11.9 meters), bundle conductor-to-ground gaps spaced 20 to 50 feet (6.1 to 15.2 meters), and bundle conductor-to-tower leg gaps spaced 14 to 29 feet (4.3 to 8.8 meters). The critical flashover voltage range is from 1100 to 2700 kV. Together with the above, the following variables were investigated: time to crest, insulator string length, rain, window-shape, tower width, conductor entrance angle, and conductor configuration. In addition, work was accomplished on standard deviation, time to flashover, and flashover patterns.
Keywords
Cables; Circuit testing; Conductors; Flashover; Insulation; Laboratories; Leg; Poles and towers; Steel; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1970.292760
Filename
4074260