DocumentCode
1041332
Title
Automatic Adjustment of Transformer and Phase-Shifter Taps in the Newton Power Flow
Author
Peterson, Norris M. ; Meyer, W. Scott
Author_Institution
Systems Control, Inc.
Issue
1
fYear
1971
Firstpage
103
Lastpage
108
Abstract
In recent years, Newton´s method has been generally accepted as a superior algorithm for solving power flow problems. But the introduction of generator var limits, area-interchange control, load-tap- changing (LTC) transformers, and variable phase shifting transformers has significantly increased the solution times (compared with a fixed system). This paper shows how LTC transformers and variable phase-shifting transformers may be automatically adjusted by the Newton algorithm, thus complementing a previous inclusion of the area interchange control variables within the Newton algorithm [1]. Tests of the new method for adjusting LTC transformers and phase shifters indicate a significant overall saving in solution time.
Keywords
Admittance; Automatic generation control; Control systems; Equations; Load flow; Newton method; Phase transformers; Power system planning; Reactive power; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1971.292904