DocumentCode :
1042394
Title :
EHV Double-Circuit Untransposed Transmission Line-Analysis and Tests
Author :
Hesse, M. Harry, Sr. ; Sabath, J.
Author_Institution :
General Electric Company
Issue :
3
fYear :
1971
fDate :
5/1/1971 12:00:00 AM
Firstpage :
984
Lastpage :
992
Abstract :
The current unbalance in two 113 mile long, electrically parallel, untransposed 500 kV overhead transmission line sections is studied for conditions in which some or all of the series-capacitor compensation is removed from individual circuits. It is shown that a negative sequence current of over 25% of the positive sequence line current can flow for certain phasing arrangements of the conductors and when one circuit is 70% series-capacitor compensated while the other circuit is uncompensated.
Keywords :
Capacitors; Circuit testing; Conductors; Distributed parameter circuits; Impedance; Particle measurements; Performance analysis; Power transmission lines; Strontium; Transmission line matrix methods;