• DocumentCode
    1042511
  • Title

    Arc Cooling and Short Line Fault Interruption

  • Author

    Swanson, B.W. ; Roidt, R.M. ; Browne, T.E., Jr.

  • Author_Institution
    Heat Transfer and Fluid Dynamics Westinghouse Research Laboratories
  • Issue
    3
  • fYear
    1971
  • fDate
    5/1/1971 12:00:00 AM
  • Firstpage
    1094
  • Lastpage
    1102
  • Abstract
    This paper covers the derivation of two sets of short line fault equations for the maximum rate of rise of recovery voltage (RRRV) characteristic of gas blast interrupters. The assumption that the electrical conductivity is proportional to the heat flux potential leads to a Cassie integral equation for post-arc current, a critical thermal time constant and the first set of RRRV equations. The assumption that the electrical conductivity varies exponentially with the heat flux potential leiads to the Mayr equation and the second set of RRRV equations. For both sets of equations it is shown that the maximum RRRV is (a) approximately proportional to the gas pressure; (b) proportional to the effective nozzle arc length at current zero and the number of series breaks; (c) proportional to temperature dependent coefficients which are functions of gas properties; and (d) inversely proportional to (dI/dt)m where m=3/2 and 1 for the "Cassie" and "Mayr" RRRV equations, respectively. These equations are complementary and serve as "first-order" limits on the interrupting capability of gas blast interrupters.
  • Keywords
    Circuit breakers; Circuit faults; Cooling; Fluid flow; Integral equations; Interrupters; Resistance heating; Temperature; Thermal conductivity; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1971.292873
  • Filename
    4074437