Economic Analysis of a Generalized Design for a Forced Cooled Cable
Author
Long, H.M. ; Notaro, J. ; Webster, D.J.
Author_Institution
Union Carbide Corporation Linde Division
Issue
3
fYear
1971
fDate
5/1/1971 12:00:00 AM
Firstpage
1232
Lastpage
1245
Abstract
The thermal ratings of forced cooled and self-cooled cable runs are reviewed in order to assess the merit of forced cooling. These ratings, along with those of forced cooled joints, are employed to show that the ampacity of a 138 kV, 2000 kc mil high pressure oil filled pipe type system can be increased by at least 100o through forced cooling by circulating the pipe oil. The refrigeration requirements to permit this increased ampacity is determined, and the flow schemes which will meet these requirements are outlined along with the generic design of a refrigeration package to implement the preferred flow scheme. This generic design is used as the basis for an economic analysis which shows that single forced cooled cable ampacities greater than the ratings of a pair of self-cooled cables can be achieved at a 20% cost saving over the use of two self-cooled cables to meet the same load requirement. The emergency ratings of these forced cooled cables which correspond to the usual 100 and 300 hour emergency ratings are found to be 8 and 6% of the 100% duty cycle rating.
Keywords
Coolants; Cooling; Environmental economics; Heat transfer; Oil filled cables; Packaging; Petroleum; Refrigeration; Soil; Thermal force;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1971.292889
Filename
4074453
Link To Document