    Economic Analysis of a Generalized Design for a Forced Cooled Cable

  • Author

    Long, H.M. ; Notaro, J. ; Webster, D.J.

  • Author_Institution
    Union Carbide Corporation Linde Division
  • Issue
    3
  • fYear
    1971
  • fDate
    5/1/1971 12:00:00 AM
  • Firstpage
    1232
  • Lastpage
    1245
  • Abstract
    The thermal ratings of forced cooled and self-cooled cable runs are reviewed in order to assess the merit of forced cooling. These ratings, along with those of forced cooled joints, are employed to show that the ampacity of a 138 kV, 2000 kc mil high pressure oil filled pipe type system can be increased by at least 100o through forced cooling by circulating the pipe oil. The refrigeration requirements to permit this increased ampacity is determined, and the flow schemes which will meet these requirements are outlined along with the generic design of a refrigeration package to implement the preferred flow scheme. This generic design is used as the basis for an economic analysis which shows that single forced cooled cable ampacities greater than the ratings of a pair of self-cooled cables can be achieved at a 20% cost saving over the use of two self-cooled cables to meet the same load requirement. The emergency ratings of these forced cooled cables which correspond to the usual 100 and 300 hour emergency ratings are found to be 8 and 6% of the 100% duty cycle rating.
  • Keywords
    Coolants; Cooling; Environmental economics; Heat transfer; Oil filled cables; Packaging; Petroleum; Refrigeration; Soil; Thermal force;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1971.292889
  • Filename
    4074453