DocumentCode :
1043015
Title :
Determination of Transient Inrush Currents in Power Transformers Due to Out-of-Phase Switching Occurrences
Author :
Nelson, P.Q. ; Benko, I.S.
Author_Institution :
Southern California Edison Company
Issue :
4
fYear :
1971
fDate :
7/1/1971 12:00:00 AM
Firstpage :
1511
Lastpage :
1521
Abstract :
This paper describes a basic method to determine the crest value of the transient inrush currents flowing in power transformer windings resulting either from imperfect synchronizing procedures or from erroneous switching operations. The currents which flow under these unusual conditions are similar in magnitude and envelope to through-short circuit faults and may, in some cases, exceed the currents which flow through transformer windings during three-phase faults on their terminals.
Keywords :
Circuit faults; Frequency synchronization; Power generation; Power transformers; Short circuit currents; Surges; Switching circuits; Thermal stresses; Transient analysis; Windings;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1971.293135