• DocumentCode
    1043137
  • Title

    Switching Surge Flashover of UHV Transmission Line Insulation

  • Author

    Kachler, A.J. ; Laforest, J.J. ; Zaffanella, L.E.

  • Author_Institution
    General Electric Company
  • Issue
    4
  • fYear
    1971
  • fDate
    7/1/1971 12:00:00 AM
  • Firstpage
    1604
  • Lastpage
    1611
  • Abstract
    The switching-surge performance of a large number of basic uhv transmission line insulation configurations has been extensively studied. The paper reports on outside phase, tower window, conductor- to-ground (with and without protrusions), conductor-to-conductor, vertical and horizontal rod-rod and rod-plane gaps. The investigated air gaps range from 10 to 66 ft (3.0 to 20.1 m) and the associated switching-surge strengths range from 1100 to 2700 kV. The paper extends earlier work1 and offers numerous design curves to the transmission line designer for uhv transmission systems up to 1500-kV system voltage.
  • Keywords
    Air gaps; Dielectrics and electrical insulation; Flashover; Leg; Poles and towers; Power transmission lines; Surges; Testing; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1971.293147
  • Filename
    4074502