Title :
Overload Classification of Secondary Network Cables Modified Test Procedure
Author :
Hunter, C.H. ; Lamberton, S.P. ; McKean, A.L. ; Zazutak, T.J.
Author_Institution :
Cincinnati Gas & Electric Co.
fDate :
7/1/1971 12:00:00 AM
Abstract :
This paper describes a new test procedure for determining the damage threshold temperature for secondary network cables. Present network cables generally have a maximum damage threshold temperature of 260°C and are protected by class L260 network limiters. The new procedure is considered suitable for evaluating cable designs for damage threshold temperatures up to 340°C, and adaptable for higher temperatures by increasing the rate of cooling of the conduit.
Keywords :
Cable insulation; Conductors; Insulation testing; Manufacturing; Polyethylene; Power industry; Round robin; Rubber; Temperature; Wire;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1971.293182