• DocumentCode
    1043489
  • Title

    Cable Installation Technique Challenging Sharp Difference in Land Elevation

  • Author

    Imai, T. ; Kikuchi, K. ; Takada, N. ; Ishizu, K.

  • Author_Institution
    The Furukawa Electric Co., Ltd.
  • Issue
    4
  • fYear
    1971
  • fDate
    7/1/1971 12:00:00 AM
  • Firstpage
    1883
  • Lastpage
    1893
  • Abstract
    The essential points of interesting technical matters concerning the design of POF cable and accessories and its installation for Grand Coulee Dam in U.S.A. are discussed. Such difficult problems as extra high oil pressure in lower side pothead, oil drainage from cable, high cable pull tension and cable sliding down were all derived from the high elevation difference and successfully solved.
  • Keywords
    Cable insulation; Meeting planning; Oil filled cables; Petroleum; Power & Energy Society; Power generation; Pressure control; Radio access networks; Rivers; Switching circuits;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1971.293183
  • Filename
    4074538