DocumentCode :
1043846
Title :
General Considerations in Grounding the Neutral of Power Systems
Author :
Dewey, H.H.
Author_Institution :
Asst. Engineer, Lighting Dept. General Electric Co.
fYear :
1923
Firstpage :
405
Lastpage :
416
Abstract :
In the early days of power transmission, there was no consistent practise in respect to operating with neutral isolated or with neutral grounded. The rapid growth of transmission systems with their extensive networks soon began to show disastrous results from arcing grounds on isolated neutral systems and now most power transmissson networks have their neutrals grounded in some manner. The discussion of general considerations of neutral grounding is divided into two parts, that of overhead line systems and underground cable systems. He brings out the fact that while most overhead systems are grounded there is some difference in practise as to the extent to which they are grounded, that is as to whether they are grounded solidly or through resistance. Prevailing practise tends toward little or no resistance. Attention is called to different possible methods of grounding a system and shows by diagrams the flow of short-circuit current with the different methods. Underground cable systems are consistently operated with neutral grounded but general practice tends toward the use of resistance in neutral. General consideration as to protection from the voltage strains due to arcing grounds on cable systems are similar to overhead line systems and the author analyzes briefly the character of cable breakdowns and general effect of such breakdowns with a view to determining the importance of the extent to which a cable system should be grounded.
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1923.5060883
Filename :
5060883
Link To Document :
بازگشت