    Anti-Pollution Design Criteria for Line and Station Insulators

  • Author

    Kimoto, Iwao ; Kito, Kuniji ; Takatori, Toshimitsu

  • Author_Institution
    NGK INSULATORS OF AMERICA, LTD.
  • Issue
    1
  • fYear
    1972
  • Firstpage
    317
  • Lastpage
    327
  • Abstract
    This paper presents anti-pollution design criteria for line and station insulators based on investigation of performance of various insulators under artificial pollution tests. Field pollution areas were classified into six classes; AA, A, B, C, D and E according to pollution degree. Recommended leakage distance for disc insulators per 1 kV of nominal line-to- line voltage are 0.75", 0.9", 1.0" and 1.1 " for A, B, C and D areas respectively. Considerable increase in leakage distance is necessary for cylindrical post insulators and porcelain shells with increase in average diameter.
  • Keywords
    Chemical analysis; Flashover; Insulation testing; Insulator testing; Laboratories; Performance analysis; Pollution measurement; Porcelain; Power transmission; Voltage;