DocumentCode
1045277
Title
Anti-Pollution Design Criteria for Line and Station Insulators
Author
Kimoto, Iwao ; Kito, Kuniji ; Takatori, Toshimitsu
Author_Institution
NGK INSULATORS OF AMERICA, LTD.
Issue
1
fYear
1972
Firstpage
317
Lastpage
327
Abstract
This paper presents anti-pollution design criteria for line and station insulators based on investigation of performance of various insulators under artificial pollution tests. Field pollution areas were classified into six classes; AA, A, B, C, D and E according to pollution degree. Recommended leakage distance for disc insulators per 1 kV of nominal line-to- line voltage are 0.75", 0.9", 1.0" and 1.1 " for A, B, C and D areas respectively. Considerable increase in leakage distance is necessary for cylindrical post insulators and porcelain shells with increase in average diameter.
Keywords
Chemical analysis; Flashover; Insulation testing; Insulator testing; Laboratories; Performance analysis; Pollution measurement; Porcelain; Power transmission; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1972.293366
Filename
4074715
Link To Document