DocumentCode
1046201
Title
Corona in Oil
Author
Crago, A.C. ; Hodnette, J.K.
Author_Institution
Westinghouse Electric & Mfg. Co., East Pittsburgh Pa.
fYear
1925
Firstpage
211
Lastpage
216
Abstract
Experiments were made to determine certain effects of high local voltage stresses in transformer oil. The resistivity of the oil was measured by a special method immediately following a period of voltage stress. The results were: 1. A greatly reduced resistivity when the stressing voltage was greater than that producing visible corona. 2. A gradual increase in resistivity following removal of stress. The ``rapidly applied´´ breakdown voltage was found for samples of oil which had been previously subjected to high voltage stresses. The dielectric strength varied in a manner similar to the resistivity, but showed an actual improvement in dielectric strength when the oil was given a rest period of 15 minutes. Definite conclusions are given at the end of the paper.
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1925.5061105