DocumentCode :
1046201
Title :
Corona in Oil
Author :
Crago, A.C. ; Hodnette, J.K.
Author_Institution :
Westinghouse Electric & Mfg. Co., East Pittsburgh Pa.
fYear :
1925
Firstpage :
211
Lastpage :
216
Abstract :
Experiments were made to determine certain effects of high local voltage stresses in transformer oil. The resistivity of the oil was measured by a special method immediately following a period of voltage stress. The results were: 1. A greatly reduced resistivity when the stressing voltage was greater than that producing visible corona. 2. A gradual increase in resistivity following removal of stress. The ``rapidly applied´´ breakdown voltage was found for samples of oil which had been previously subjected to high voltage stresses. The dielectric strength varied in a manner similar to the resistivity, but showed an actual improvement in dielectric strength when the oil was given a rest period of 15 minutes. Definite conclusions are given at the end of the paper.
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1925.5061105
Filename :
5061105
Link To Document :
بازگشت