Transient Oil Pressure Rise at EHV Pipe-Type Cable Faults
Author
Murakushi, Yoshimasa ; Fukagawa, Hiromasa ; Uchiyama, Takuji
Author_Institution
No. 1 Technical Laboratory, Central Research Institute of Electric Power Industry
Issue
4
fYear
1972
fDate
7/1/1972 12:00:00 AM
Firstpage
1339
Lastpage
1345
Abstract
Since various phenomena resulting from earth faults in pipe-type cables have not yet been sufficiently clarified, the authors made fault tests on pipes of 105 and 254 mm in diameter and 20 to 60 m in length. As a result, arc voltages were found to be nearly constant, independent of the magnitude of fault current. Moreover, the mechanism of transient pressure rise and the relation between arc energy and oil pressure rise were elucidated. Calculated results agreed fairly well with experimental data.
Keywords
Communication cables; Conductors; Earth; Fault currents; Mechanical cables; Oil filled cables; Petroleum; Steel; Testing; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1972.293263