DocumentCode :
1047042
Title :
60 HZ Behaviour of Vaccum Insulation in High Voltage Switchgear
Author :
Erven, Clifford C. ; van Heeswijk, R.G. ; Srivastava, K.D.
Author_Institution :
The Hydro-Electric Power Commission of Ontario
Issue :
4
fYear :
1972
fDate :
7/1/1972 12:00:00 AM
Firstpage :
1589
Lastpage :
1596
Abstract :
Vacuum has special properties which make it a potentially good insulating medium for the power industry but high voltage 60 Hz performance data is lacking. Experimental data is presented on the 60-Hz behaviour of vacuum insulation for gap lengths 0.5 to 2.0 cm between metal electrodes in a dynamically pumped system operating at 10-6 torr. The results are compared with the dc characteristics of vacuum insulation for similar test conditions. Prebreakdown phenomena and protrusion formations under 60 Hz voltage stress appear to be distinctly different. Specific recommendations are set out to guide further research effort, and to meet the particular requirements of vacuum insulation for high voltage power apparatus.
Keywords :
Breakdown voltage; Circuits; Electrodes; Gas insulation; Insulation testing; Power industry; Stress; Switchgear; Vacuum breakdown; Vacuum systems;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1972.293312
Filename :
4074892
Link To Document :