Abstract
The performance of two fog-type porcelain insulators is investigated in the case of condensation wetting and uniform as well as non-uniform contaminant distribution. Both insulators have been employed simultaneously on the same transmission line poles and exceed the minimum required creepage distance. However, their field performance was remarkably different. The analysis performed indicates that, in the case of condensation, the total creepage distance is exposed to wetting, including the parts that are considered ´protected´ along the fog-type profile. In addition, these parts tend to accumulate more pollution, resulting in an inferior insulator performance. Consequently, for the specific environmental conditions, in addition to the creepage distance, the insulator profile is a parameter that greatly influences the service performance and therefore must also be considered in the selection of an insulator.
Keywords
condensation; high-voltage engineering; insulator contamination; porcelain insulators; wetting; coastal high voltage networks; condensation wetting; creepage distance; fog-type porcelain insulators; insulator profile; nonuniform contaminant distribution; transmission line poles; uniform contaminant distribution;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings -
Publisher
iet
ISSN
1350-2344
Type
jour
DOI
10.1049/ip-smt:20050050
Filename
1659657
Link To Document