Title
The Transient Recovery Voltage Application of Power Circuit Breakers
Author
Colclaser, R.G.
Author_Institution
University of Pittsburgh
Issue
5
fYear
1972
Firstpage
1941
Lastpage
1947
Abstract
The proposed transient recovery voltage standard for high voltage circuit breakers will specify application requirements on a recovery voltage basis. This paper studies the inherent circuit parameters required to generate the required TRV envelope. A simplified application procedure is developed based on miles to the first line discontinuity and the number of lines connected on the bus side of the circuit breaker.
Keywords
Circuit breakers; Circuit faults; Interrupters; Petroleum; Power system faults; Power system transients; Temperature; Testing; Transient analysis; Voltage;