• DocumentCode
    1048721
  • Title

    Forced Air Cooled Isolated Phase Bus-Experimental Verification of Design Parameters

  • Author

    Aslam, Moudood A. ; Meyers, Francis G. ; Trivedi, Ramesh C.

  • Author_Institution
    H. K. PORTER CO., INC.
  • Issue
    1
  • fYear
    1973
  • Firstpage
    212
  • Lastpage
    221
  • Abstract
    Currently 1300 MW machines are being installed in power plants and 1500 and 2000 MW machines are a distinct possibility. Consequently isolated phase bus in power plants has to carry continuous currents as high as 40,000 amps or more. In this paper the results of tests conducted under laboratory conditions up to 36,000 amps is analyzed and discussed. An empirical approach for determining time-temperature behavior under emergency conditions, such as failure of cooling equipment, is suggested. The detailed design of a forced cooling system for isolated phase bus is discussed.
  • Keywords
    Coils; Cooling; Costs; Fans; Heat transfer; Laboratories; Power generation; Temperature; Testing; Water heating;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1973.293615
  • Filename
    4075059