DocumentCode :
1049979
Title :
Research at Project UHV on the Performance of Contaminated Insulators Part II - Application to Practical Design
Author :
Kawai, Mikio
Author_Institution :
General Electric Company
Issue :
3
fYear :
1973
fDate :
5/1/1973 12:00:00 AM
Firstpage :
1111
Lastpage :
1120
Abstract :
Results of full-scale tests on V-suspension strings up to 50 standard insulators (about 24-ft long) are presented and the need of such tests is demonstrated. Because of pronounced nonlinearity on standard insulator strings, the use of large disc insulators is recommended for UHV line insulation. A practical design method for anti-contamination design is developed on a statistical basis.
Keywords :
Conductors; Contamination; Design methodology; Dielectrics and electrical insulation; Flashover; Insulation testing; Insulator testing; Laboratories; Proximity effect; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1973.293678
Filename :
4075180
Link To Document :
بازگشت