DocumentCode
1050208
Title
Generator I22t Requirements for System Faults
Author
Brown, P.G.
Author_Institution
General Electric Company
Issue
4
fYear
1973
fDate
7/1/1973 12:00:00 AM
Firstpage
1247
Lastpage
1251
Abstract
The design of turbine generators is strongly influenced by their requirements for negative sequence duty. In conjunction With a current revision to the ANSI C-50 standards, a review was made of the system requirements for I22t capability in generators of directly cooled sizes, tied into high voltage transmission systems. The results of these studies, which is the subjict of this paper, indicate that maximum expected I22t duty for system faults is less than two, or roughly one-third of the lowest I22t values specified in the revised standard, indicating also that a comfortable margin will still exist between system requirements and machine capabilities.
Keywords
ANSI standards; DC generators; Delay effects; Iron; Power generation; Rotors; Stability; Temperature; Turbines; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1973.293807
Filename
4075201
Link To Document