• DocumentCode
    1050747
  • Title

    Inductive Test Circuit for a Fast Acting HVDC Interrupter

  • Author

    Hofmann, G.A. ; Long, W.F. ; Knauer, W.

  • Author_Institution
    Hughes Research Laboratories
  • Issue
    5
  • fYear
    1973
  • Firstpage
    1605
  • Lastpage
    1614
  • Abstract
    A unique test facility utilizing the inductive energy storage principle has been constructed in order to examine the characteristics of a fast acting HVDC interrupter. The facility is capable of producing currents up to 10, 000 A, developing voltages up to 200 kV, and storing energies up to 125 kJ. It is able to closely simulate the operational stresses encountered in the interruption of dc current. Experimental and computer results illustrate the operating characteristics of the facility.
  • Keywords
    Circuit breakers; Circuit faults; Circuit testing; HVDC transmission; Impedance; Interrupters; Stress; Switches; Switching circuits; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1973.293708
  • Filename
    4075254